VEGAFLEX: Guided Wave Radar 

In this type of radar level measurement, microwave pulses are conducted along a cable or rod probe and reflected by the product surface. The measuring probe of the TDR sensor ensures that the signal reaches the medium undisturbed. Liquids, solids and separation layers (interfaces) in liquids are commonly measured with this measuring technique.
The advantages
The TDR sensors measure reliably even with:
Steam generation
Pressure and temperature fluctuations
Dust and noise
Condensation
 
VEGAFLEX 81
Version: exchangeable cable probe (ø 2 mm, ø 4 mm); exchangeable rod probe (ø 8 mm);coax probe (ø 21.3, mm, ø 42 mm)
Measuring range:cable probe up to 75 m;rod probe up to 6 m;coax probe up to 6 m
Process fitting:thread from G¾, ¾ NPT flanges from DN 25, 1"
Process temperature:-40 … +200 °C
Process pressure:-1 … +40 bar(-100 … +4000 kPa)
Accuracy:+/- 2 mm
 
VEGAFLEX 83
Version:cable probe (ø 4 mm),rod probe (ø 8 mm)
Measuring range:cable probe up to 32 m;rod probe up to 4 m
Process fitting:flanges from DN 25, 1"hygienic fittings
Process temperature:-40 … +150 °C
Process pressure:-1 … +16 bar(-100 … +1600 kPa)
Accuracy:+/- 2 mm
 
VEGAFLEX 86
Version: exchangeable cable probe (ø 2 mm, ø 4 mm) exchangeable rod probe (ø 16 mm) coax probe (ø 42 mm)
Measuring range:cable probe up to 75 m,rod probe up to 6 m,coax probe up to 6 m
Process fitting:thread from G1½ , 1½ NPT flanges from DN 50, 2"
Process temperature:-196 … +450 °C
Process pressure:-1 … +400 bar (-100 … +40000 kPa)
Accuracy:+/- 2 mm
 
VEGAFLEX 61
Version:exchangeable cable (ø 2 mm, ø 4 mm),exchangeable rod (ø 6 mm)
Measuring rangecable: up to 32 m,rod: up to 4 m
Process fitting thread from G¾, ¾ NPT flanges from DN 25, 1"
Process temperature:-40 … +150 °C
Process pressure:-1 … +40 bar (-100 … +4000 kPa)
Accuracy:+/- 3 mm
SIL qualification up to SIL2
 
VEGAFLEX 62
Version:exchangeable cable (ø 6 mm),exchangeable rod (ø 16 mm)
Measuring range:cable: up to 60 m,rod: up to 6 m
Process fitting thread from G1½, 1½ NPT flanges from DN 50, 2"
Process temperature:-40 … +150 °C
Process pressure:-1 … +40 bar (-100 … +4000 kPa)
Accuracy:+/- 3 mm
SIL qualification up to SIL2
 
VEGAFLEX 63
Version:cable (ø 4 mm) rod (ø 10 mm)
Measuring range:cable up to 32 m,rod up to 4 m
Process fitting flanges from DN 50, 2“ Clamp from 1"
Process temperature:-40 … +150 °C
Process pressure:-0.5 … +16 bar (-50… +1600 kPa)
Accuracy:+/- 3 mm
SIL qualification up to SIL2
 
VEGAFLEX 65
Version coax probe
Measuring range: up to 6 m
Process fitting thread from G¾, ¾ NPT flanges from DN 25, 1"
Process temperature:-40 … +150 °C
Process pressure:-1 … +40 bar (-100 … +4000 kPa)
Accuracy:+/- 2 mm
SIL qualification up to SIL2
 
VEGAFLEX 66
Version exchangeable cable (from ø 4 mm),exchangeable rod (from ø 6 mm) coax probe Measuring
range cable up to 60 m,rod up to 6 m,coax up to 6 m
Process fitting thread from G¾, ¾ NPT flanges from DN 40, 2"
Process temperature:-200 … +400 °C
Process pressure:-1 … +400 bar (-100 … +40000 kPa)
Accuracy from: ±3 mm
SIL qualification up to SIL2
 
VEGAFLEX 67
Version:exchangeable cable (ø 4 mm),exchangeable rod (ø 6 mm) coax probe
Measuring range:cable up to 60 m,rod up to 6 m coax up to 6 m
Process fitting thread from G¾, ¾ NPT flanges from DN 25, 1"
Process temperature:-200 … +400 °C
Process pressure:-1 … +400 bar (-100 … +40000 kPa)
Accuracy:±10 mm

 